Guangzhou Rong 'an Fire Equipment Co., LTD
Mr. Chen's telephone number:13928768802
Mr. Huang's telephone number:13711155165
Landline telephone:Landline telephone:020-31143089
Fax:020-31143992
E-mail:1851885478@qq.com
Website:http://www.gzrongan.net
Address: 15 Yongfeng Road, Shawan Town, Panyu District, Guangzhou City, Guangdong Province
The gas fire extinguishing system is divided into two types: pipe network and no pipe network. The pipe network includes internal storage pressure and external storage pressure. Today, we will talk about the differences between the internal storage pressure and external storage pressure of HFC-227ea.
First, transmission distance:
In general, the transmission distance of 2.5mpa pressure class pipeline is less than or equal to 32m, the transmission distance of 4.2mpa pressure class pipeline is less than or equal to 55m, and the transmission distance of 5.6mpa pressure class pipeline is less than or equal to 80m. The transmission distance greatly limits the application of HFC-227ea fire extinguishing system. The birth of external storage pressure is a good solution to solve this problem. The system action, fire extinguisher group, fire extinguishing agent group by special inflator cylinder group according to its stamping and conveying of HFC-227EA reagent design pressure is 4.2MPa, the maximum transport distance can be more than 240m.
Here we look at the parameters of external storage pressure:
According to the current national standard, the filling density of HFC-227ea fire extinguishing system with internal storage pressure is: 2.5MPa system should not be greater than 1120kg/m3 (steel welded gas cylinder); 4.2MPa system shall not be greater than 950kg/m3 (steel welded gas cylinder); 5.6MPa system should not be larger than 1080kg/m3 (steel seamless cylinder). 4.2MPa external storage pressure system shall not be greater than 1250kg/m3.
Technical parameters:
System main technical parameters
System implementation standard | Q/RXF 1-2014 | |||
Storage pressure (20℃, MPa) | 0.3 | |||
Extinguishing agent cylinder group volume (L) | 90 | 120 | 150 | 180 |
System injection time (s) | ≤10 | |||
Maximum filling rate of extinguishing agent(Kg/m3) | 1250 | |||
Operating temperature of the system (° C) | 0~50 | |||
System working pressure (20℃) (MPa) | 4.2 | |||
System maximum working pressure (MPa) | 5.3 |
Temperature (℃) | pressure Mpa (20 ° C) | Power supply | |||
Design temperature | Service temperature | Fire extinguishing agent bottle group | Nitrogen drive bottle set | Main electricity | Backup power |
0~50 | 0~50 | 0.3 | 13.5 | AC 220v | DC 24V |
Bottle group name | Model Specification (L) | Storage pressure (20℃) | |||
Nitrogen starting bottle set | 8L | 6MPa | |||
Nitrogen power cylinder set | 70L | 13.5MPa | |||
Fire extinguishing agent bottle group | 90 | 120 | 150 | 180 | 0.3MPa |
Finally, the nitrogen power bottle group is added to the external pressure storage system, which increases a pushing pressure to the delivery of the agent, so the transmission distance is relatively long.
The above articles are organized and published by Guangzhou Rong 'an Fire Equipment Co., LTD.
Copyright © 2015 www.gzrongan.net Guangzhou Rong 'an Fire Equipment Co., LTD All rights reserved
Contact: Mr. Chen Phone:13928768802 Mr. Huang Phone:13711155165 Tel:020-31143089 Fax:020-31143992 Email:1851885478@qq.com Address: 15 Yongfeng Road, Shawan Town, Panyu District, Guangzhou City, Guangdong Province Registration license No. :粤ICP备16114979号